1-54
1
1
CAUTION
7. HOW TO INSTALL THE OUTDOOR UNIT
1. Installing the Outdoor Unit
Use concrete or a similar material to make the base,
and ensure good drainage.
Ordinarily, ensure a base height of 5 cm or more.
If a drain pipe is used, or for use in cold-weather
regions, ensure a height of 15 cm or more at the feet
on both sides of the unit.
(In this case, leave clearance below the unit for the
drain pipe, and to prevent freezing of drainage water
in cold-weather regions.)
Refer to Fig. 1-21 for the anchor bolt dimensions.
Be sure to anchor the feet with anchor bolts (M10).
In addition, use anchoring washers on the top side.
(Use large square 32 × 32 SUS washers with JIS
nominal diameter of 10.) (Field supply)
For 8 and 10 HP unit
13
40
340
60
13
110
660
170
75
75
219
105
290
26
38
0
20
10
41
0
18
Air Intake
Air
Intake
Air discharge
2- o32 Specified drain port
940
Drain port
Anchor bolt (M10)
Fig. 1-21
Fig. 1-22
2. Drainage Work
Follow the procedure below to ensure adequate draining
for the outdoor unit.
For the drain port dimensions, refer to Fig. 1-21.
Ensure a base height of 15 cm or more at the feet on
both sides of the unit.
3. Routing the Tubing and Wiring
The tubing and wiring can be extended out in 4 directions:
front, rear, right, and down.
The service valves are housed inside the unit.
To access them, remove the inspection panel.
(To remove the inspection panel, remove the 3 screws,
then slide the panel downward and pull it toward you.)
(1)
(2)
If the routing direction is through the front, rear, or right,
use a nipper or similar tool to cut out the knockout holes for
the inter-unit control wiring outlet, power wiring outlet, and
tubing outlet from the appropriate covers A and B.
If the routing direction is down, use a nipper or similar tool
to cut out the lower flange from cover A. (Fig. 1-22)
Route the tubing so that it does not contact the compressor, panel, or other parts
inside the unit. Increased noise will result if the tubing contacts these parts.
When routing the tubing, use a tube bender to bend the tubes.
In cold-weather regions, in order to prevent drainage water from freezing, do not
install the drain socket cap. Also take steps to prevent water from accumulating
around the unit.
1.
2.
3.
Inter-unit control wiring
outlet
Inspection panel
Power wiring outlet
Cover A
Tubing outlet
Cover B
Right
Down
Rear
Front
Unit: mm
Sec1.indd 54
2014/11/07 10:28:03
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...