(5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”]
Sensor trouble
No
Are the
connectors of the sensor
020 (C2), 021 (C1), 022 (TS),
023 (TO) and 024 (TD) connected
correctly to the outdoor unit
control PCB ?
Yes
Start of defect diagnosis
Correct the connections.
Are the characteristics
of resistance values of the
sensors C2, C1, TS, TO and TD
sensors normal? *
Replace the sensors C2, C1, TS, TO
and TD.
No
Yes
Check the outdoor unit control PCB.
Replace if PCB has failed.
* Refer to “5-5. Table of Thermistor Characteristics.”
SM830194-04_Single_BigPAC.indb 12
2014/11/13 18:18:56
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...