Item code
Item
Description
1F
(Upper limit)
20
(Lower limit)
Change to the
remote control
temperature
setting range
Cooling
This setting changes the temperature range (upper limit and lower
limit) which is set from the remote controller or central control device.
The set upper limit must be greater than or equal to the lower limit.
If the temperature setting is to be a single point, set the upper limit
and lower limit to the same temperature.
21
(Upper limit)
22
(Lower limit)
Heating
23
(Upper limit)
24
(Lower limit)
Drying
25
(Upper limit)
26
(Lower limit)
Auto
heat/cool
29
Humidifier operation which
ignores the heat exchanger
temperature
During heating operation, the humidifier operates when the heat
exchanger temperature is suitable for humidifying. This setting is
used to ignore this condition for humidifier operation and operate the
humidifier more.
2A
Filter input switching
This setting switches the filter input according to the purpose of use.
2C
Indoor unit electronic
control valve
This setting indicates whether or not an indoor unit electronic control
valve is present.
At the time of shipping, this setting is set according to the conditions
of the indoor unit.
2E
T10 terminal input switching
Ordinarily, the T10 terminal is used as the HA terminal at the time
of shipping. However, this setting is used when the T10 terminal is
used for OFF reminder or for fire prevention input.
31
Ventilation fan operation
from remote controller
It is possible to install a ventilation fan in the system, which can be
started and stopped by the wired remote controller. The ventilation
fan can operate linked with the start and stop of the indoor unit, or
can be operated even when the indoor unit is stopped.
Use a ventilation fan that can accept the no-voltage A contact as the
external input signal.
In the case of group control, the fans are operated together. They
cannot be operated individually.
32
Switching to remote
controller sensor
This setting is used to switch from the body sensor to the remote
controller sensor.
Check that “remote controller sensor” is displayed.
Do not use this setting with models that do not include a remote
controller sensor.
Do not use this setting if both the body sensor and remote sensor
are used.
34
ON/OFF of “Operation
change control in progress”
display
In a MULTI system with multiple remote controllers, switching
between heating and cooling is restricted, and “Operation change
control in progress” is displayed.
This setting is used to prevent this display from appearing.
Refer to the item concerned with operating mode priorities.
35
OFF reminder function for
weekly timer
This setting switches the operation when the weekly timer is
connected to the remote controller.
This can be used to prevent cases in which the unit is accidentally
left ON. There is no change when this setting is ON, however it is
necessary to set the weekly timer ON time.
(Continued)
7-12
SM830194-04_Single_BigPAC.indb 12
2014/11/14 14:38:37
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...