Precautions for Installation in Heavy Snow Areas
(1) The platform should be higher than the max. snow depth. (Fig. 1-19)
(2) The 2 anchoring feet of the outdoor unit should be used for the platform, and the platform should be installed
beneath the air intake side of outdoor unit.
(3) The platform foundation must be firm and the unit must be secured with anchor bolts.
(4) In case of installation on a roof subject to strong wind, countermeasures must be taken to prevent the unit from
being blown over.
Fig. 1-20
Duct
Duct
Outdoor
Unit
Air Intake
Higher than the maximum
snow depth
Air Intake
About 1/2 of the unit height
Platform (foundation)
Outdoor Unit
Duct
Min. 100
166
308
unit : mm
Min. 100
Air Discharge Chamber for Top Discharge
Be sure to install the air discharge chamber in the field
when:
It is difficult to keep a space of min. 1 m between the air discharge
outlet and an obstacle.
The air discharge outlet is facing to the sidewalk and discharged hot
air annoys the passers-by. (Fig. 1-18)
Air discharge
Fig. 1-18
Installing the Unit in Heavy Snow Areas
I
n locations with strong wind, snow-proof ducting should likewise be
fitted and direct exposure to the wind should be avoided as much as
possible.
Countermeasures against snow and wind
In regions with snow and strong wind, the following problems may
occur when the outdoor unit is not provided with a platform
and snow-proof ducting (Fig. 1-19):
a) The outdoor fan may not run and damage of the unit may be caused.
b) There may be no air flow.
c) The tubing may freeze and burst.
d) The condenser pressure may drop because of strong
wind, and the indoor unit may freeze.
In regions with significant snowfall, the outdoor unit should
be provided with a platform and snow-proof duct.
Fig. 1-19
Without snow-
proof ducting
(Low platform)
With snow-
proof ducting
(High platform)
Sec1.indd 43
2014/11/07 10:28:00
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...