2-14. Table of Self-Diagnostic Functions and Corrections
Wired remote
controller
display
(Field supply)
Indoor unit
receiver lamp
Cause
Correction
1:1 connection (Single type)
Group connection
(Simultaneous multi
system)
Nothing is
displayed
Nothing is
displayed
• Indoor operation switch is OFF.
• Indoor unit power is not ON.
• Same at left.
• Set the indoor operation switch ON.
• Turn ON the indoor unit power.
E01
displayed
Operating lamp
is blinking.
• Automatic address setting has not
been completed.
• Inter-unit control wiring is cut or is
not connected correctly.
• Same at left.
• Check the inter-unit control wiring.
• Perform automatic address setting
(See 2-15).
E14
—
—
—
—
—
—
• Remote controller
communication wiring is
cut or is not connected
correctly.
• Check the remote controller communication
wiring.
• Perform automatic address setting again.
E04
displayed
displayed
Standby lamp is
blinking
.
• Indoor-outdoor inter-unit wiring is
not connected correctly.
• Same at left.
• Connect the wiring correctly.
E06
—
—
—
—
—
—
• Inter-unit control
wiring is cut or is not
connected correctly.
• Refer to 2-15 System Control, and make
the correct settings.
E15
displayed
displayed
• Indoor unit capacity is too low.
• Same at left.
• Check that the total capacities of the indoor
and outdoor units are appropriate.
E16
displayed
• Indoor unit capacity is too high.
• Same at left.
• Reverse 2 phases of the outdoor unit
3-phase power and connect them correctly.
P05
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
• Same at left.
• Connect the units correctly.
L02
displayed
Both the
Operation lamp
and Standby
lamp are blinking
together.
• Indoor-outdoor unit type mismatch.
• Same at left.
• Connect the units correctly.
L13
displayed
• Indoor-outdoor units are not setting
correctly.
• Same at left.
• Connect the units correctly.
L04
—
—
—
—
—
—
• Outdoor unit address is
duplicated.
• Connect the units correctly.
L07
—
—
—
—
—
—
• Remote controller
communication wiring is
connected to the indoor
unit, however, it is set
for individual operation.
• Perform automatic address settin
g
(See 2-15).
P15
displayed
displayed
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• Check the refrigerant cycle (for gas
• Same at left
• No ga
s
leaks).
SM830194-04_Single_BigPAC.indb 11
2014/11/04 13:45:14
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...