6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History
* Displays outdoor unit alarms only. Does not display indoor unit alarms.
* Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device.
<Operating procedure>
(1) Press and hold the
button and
button simultaneously for 4 seconds or
longer to change to outdoor unit alarm history mode.
During the alarm history display, “Service Check” is lit.
The display and operations are the same as the monitoring of the alarm device
history that is performed using the unit remote controller. However, the outdoor
unit address appears instead of the unit No.
↓
(2) Press the
button and select the outdoor unit for alarm history monitoring.
↓
(3) Use the temperature setting
and
buttons to select the item code for the alarm history.
The display shows the address of the selected outdoor unit, the item code, and the alarm history (alarm data).
The outdoor unit address is displayed as system XX-YY.
System XX = Outdoor unit system address
↓
YY = Outdoor unit sub-bus address
The item code is displayed as 01 – 08. 01 indicates the most recent alarm.
The alarm history is indicated by the alarm code. (If there have been no alarm codes, “
” is displayed.)
(4) To clear the alarm history, press the
button. (The outdoor unit alarm history will be cleared.)
↓
(5) To end, press the
button. The display returns to the normal remote controller display.
6-6. Settings Modes: Setting the Outdoor Unit EEPROM
Setting mode 1
<Operating procedure>
(1) Press and hold the
button and
button simultaneously for
4
seconds or longer.
(2) Use the temperature setting
and
buttons to
change the item code. The item codes and setting data are
shown in the
table of “List of Item Codes” on the next page.
(3) Use the timer time
and
buttons to change the setting
data.
To confirm the changed setting data, press the
button.
(At this time, “Setting” stops blinking and remains lit.)
(4) During this mode, “Setting” is displayed, blinking. The outdoor
unit address display section displays “ALL,” the item code and
number (DN value in the table), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The display changes
between the first 3 digits (Fig.
A
) and the last 3 digits (Fig.
B
).
When the first 3 digits are displayed, the top point of the colon is
lit.)
(5) To end the setting mode, press the
button.
(3)
(1)
(4) (2)
(5)
are displayed alternately.
Displa
y of first 3 digits
A
B
Displa
y of last 3 digit
s
and
(Example shows displa
y of 000 001.
)
A
B
(3)
(1)
(2)
(5)
(3)
(1)
(2)
(5)
Display of first 3 digits
Display of last 3 digits
are displayed alternately.
(Example shows display of 000 001.)
SM830194-04_Single_BigPAC.indb 7
2014/10/31 13:21:24
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...