Start of defect diagnosis
No
No
No
1. Potential Causes
• Refrigerant overcharge
Has the refrigerant been overcharged?
*Verifying Overcharge
There is no problem if the difference between the temperature on the indoor unit "E2" and
the saturated temperature of the outdoor unit's gas pipe service valve pressure is within 2
during the heating mode. Any of the following could be the reason if the former is two or
more degrees lower than latter.
• Faulty operations of the outdoor unit electronic expansion valve.
• Pipe blockage, crushed pipes, etc.
(Assumed to be on the liquid pipes during the cooling mode and the gas pipes during the
heating mode.)
• C1 and C2 thermistor error on the outdoor unit (during the cooling mode.)
• E1 and E2 thermistor error on the indoor unit (during the heating mode.)
2.Temperature on the high-pressure side during normal operations.
Cooling: Temperature of the C2 thermistor on the outdoor unit is approximately between
45 and 55 .
Heating: Temperature of the E2 thermistor on the indoor unit is approximately between
40 and 50 .
* There are cases in which the above temperatures will be lower depending on the operation
conditions.
(2) [Alarm “P26”]
Implement the same check processes for to in the diagnosis flow of alarm P29.
No (alarm P26 output)
Replace the HIC PCB.
Yes
Yes
Yes
Yes
Yes
(Not operating
on high load)
(An alarm other than the alarm P26 occur)
Is the power voltage correct?
Was everything OK when
to in the diagnosis
flow of alarm P29 were
checked?
Is the high-pressure
for the refrigerant cycle within
the range? (High load
operating?)
Does the alarm
P26 occur when the
U / V / W wires (pink/white/blue)
are disconnected from the
HIC PCB and
operation was
started?
Was everything OK
when to in the diagnosis
flow of alarm P29 were
checked?
Replace the compressor
Correct the connection between the HIC PCB and heat sink.
Operating on high load.
Recovery methods differ in accordance with the cause.
•
Recharge refrigerant
•
Replace the thermistor
•
Repair the pipes, etc.
Implement the same check processes for to in the diagnosis flow of alarm P29.
Abnormal temperature rise in the HIC PCB is prevented by radiating the heat, with HIC being
coated evenly with thermal conduction putty and the heat sink being attached firmly to the
HIC PCB by screws. The HIC PCB cannot radiate heat properly if the screws are loose or the
thermal conduction putty is not applied correctly. Consequently, the temperature inside the HIC
PCB can rise abnormally and the alarm P26 occurs.
The HIC PCB is considered faulty if the alarm P26 occurs even if the compressor is not
operating owing to the U, V and W wires being disconnected.
Replace the HIC PCB.
Potential problems are most likely in accordance with the following sequence when it is
determined that the PCB is trouble with an alarm P26.
1. HIC PCB
2. Outdoor unit control PCB
3. Filter PCB
Replace the relevant PCBs in accordance with the above sequence.
Start-up failure of the compressor (will not start up)
Related parts
• HIC PCB (Model: [U-200PE1E8, U-250PE1E8] HIC-C906VH8)
• Outdoor unit control PCB (Model: [U-200PE1E8, U-250PE1E8] CR-C906VH8P)
• Filter PCB (Model: [U-200PE1E8, U-250PE1E8] FIL-C906VH8)
SM830194-04_Single_BigPAC.indb 9
2014/11/13 18:18:55
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...