5-5
5
5
5-3. Symptoms and Parts to Inspect
Remote
controller
alarm display
Alarm
contents
Judgement conditions
Eliminating
condition of alarm
Judgement and correction
P03
Abnormal discharge
temperature error.
•Discharge temp.
detected at or above
the specified value.
Stops when temp. exceeds
115 .
Alarm output on 4 pre-trips.
Recovery at restart
1. Check refrigerant cycle (gas
leak).
2.Trouble with electronic
expansion valve.
3.Check discharge
temperature sensor (TD).
P05
Missing phase
detected.
(CT disconnected
or AC power supply
error)
The current value transmitted
from the microcomputer on the
outdoor unit control substrate is
low.
When no AC power input for
more than 3 minutes: Pre-trip 5
times.
Recovery at restart
1.Check R/S/T power supply.
2.Check HIC circuit.
3. Check outdoor unit control
PCB.
P15
Insufficient gas level
detected.
•Discharge temperature is 100
or higher.
•Electronic expansion valve is at
Step 960.
•The current value from the MDC
is 6.0A (three-phase) / 3.5A
(single-phase) or less.
When the above has continued
for 1 minute.
Recovery at restart
1.Check refrigerant cycle (gas
leak).
2.Trouble with electronic
expansion valve.
3.Check outdoor unit valve
opening.
P19
4-way valve locked
trouble.
•Judged after
5 minutes had
elapsed since the
compressor was
switched on.
The indoor unit heat exchanger
temperature drops even
though the compressor is
switched on during the heating
mode.[min(E1,E2)] is 10
or lower.The indoor unit heat
exchanger temperature rises
even though the compressor is
switched on during the cooling
mode.E2 is 50 or higher Pre-
trip 2 times
Recovery at restart
1. Check 4-way valve.
2. Check 4-way valve wiring.
3. Check outdoor unit control
PCB.
P20
High-pressure
protection error
caused by cooling
high-load max (C1,
C2) temperature.
Halted if the temperature
exceeds 64 .
Error output on 4 consecutive
pre-trips.
Recovery at restart
1.Overload operation of
refrigerant cycle.
2.Check outdoor unit heat
exchanger temperature
sensor C1 and C2.
P22
Outdoor unit fan
motor trouble.
•Inverter protection
circuit was
activated, or lock
was detected at
outdoor unit fan
motor.
Inverter stops after alarm is
detected. Pre-trip 4 times
Recovery at restart
1.Position detection trouble.
2.Outdoor unit fan motor over-
current Protection circuit is
activated.
•Check outdoor unit control
PCB.
•Refer to outdoor unit fan
judgement methods.
P26
Inverter protector
circuit was activated.
G-Tr short-circuit
within the HIC
circuit.(Short time /
0.8 seconds or less)
HIC temperature
protection
Inverter stops after alarm
is detected. Alarm is output
when inverter stops (pre-trip)
consecutively 4 times.
Recovery at restart
Temperature dropped
1.Stops immediately even
when operations restarted.
•Layer short on the
compressor
2.Check HIC circuit.
•Wiring trouble
3.Heat sink and PCB (HIC)
•Contact trouble
SM830194-04_Single_BigPAC.indb 5
2014/11/13 18:18:54
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...