4-5
4
4
Frost adherence detection
• If the following conditions are satisfied during heating
operations, it is regarded as "frost adherence is
detected".
• Frost adherence detection is performed in accordance
with the outdoor air temperature (TO) and the outdoor
heat exchanger temperature sensor (C1).
* However, frost adherence detection is not performed
for the first 15 minutes of compressor operations in
the normal heating mode.
• Frost adherence detection conditions
(a) With the outdoor air temperature (TO) being -13
°C
or above, the frost adherence condition shown
below are satisfied for whether 3 consecutive
minutes or a total of 60 intermittent minutes, or
the outdoor heat exchanger temperature sensor
(C1) remains -18
°C
or below for 20 consecutive
seconds.
(b) With the outdoor air temperature (TO) being less than
-13
°C
, the outdoor heat exchanger temperature
sensor (C1) remains less than or equal to outdoor air
temperature (TO) - 5
°C
for 20 consecutive seconds.
(c) With the outdoor heat exchanger temperature sensor
(C1) being less than - 3
°C
, a total of 90 minutes
has elapsed (defrosting carried out periodically in
accordance with the time).
7) Discharge Temperature Control
The following control is performed to prevent the discharge temperature from rising abnormally in order to
protect the inverter compressor. In accordance with the temperature of the discharge sensor TD, such controls
are performed as to limiting the increase of inverter frequency, decreasing it or halting operation of the
compressor.
TD (discharge)
115
105
100
95
80
-13
0
Y
10
-3
-8
-19.4
X
* If the discharge temperature exceeds 115°C , operations of the compressor are halted and then
restarted 3 minutes later.
If this start/stop activity is repeated 4 times consecutively, the alarm "P03" (abnormal discharge
temperature) occurs.
8) Defrosting Control
This control function removes frost that has adhered to the outdoor heat exchanger during the heating operation.
The control is performed to prevent the deterioration of the heating capabilities attributed to the adherence of
frost, and to prevent the crack or crush of pipes attributed to the accretion of ice.
The following control is performed in accordance with the external temperature and the outdoor heat exchanger
temperature sensor (C1).
Overall Flow Chart of Defrosting Control
Outdoor unit operation halted
Frequency decreased
Frequency increases prevented
Frequency increased slower than usual
Normal (no control)
Normal heating operation
Has frost adherence been
detected?
1
Has more than 25 minutes
(heating mask time) elapsed?
2
Have the conditions for ending
defrosting been satisfied?
3
Heating operation resumed
Yes (satisfied)
Yes (elapsed)
Heating
operation
continued
Heating
operation
continued
Defrosting
operation
continued
Yes (detected)
Defrosting operations commenced
Outdoor heat exchanger temperature sensor (C1) (°C)
Outdoor air temperature (TO) (°C)
Defrosting condition zone
No
No
No
SM830194-04_Single_BigPAC.indb 5
2014/10/31 11:25:39
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...