5-2. Contents of LED Display on the Outdoor Unit Control PCB
LED 1
LED 2
Remarks
Power ON sequence
1. No communication from indoor units in system
2. Communication received from 1 or more indoor units in system
3. Regular communication OK (Capacity and unit quantity match)
If it is not possible to advance to 3,
repeats 1 2.
At 3, changes to normal control.
Normal operation
Displayed during automatic address
setting 1 and initial communication.
After these are completed, alarm F31 is
displayed.
EEPROM error (F31)
Pre-trip (insufficient gas)
Pre-trip (P20)
Pre-trip (other)
(0.25/0.75)
(0.25/0.75)
P03
Alarm
Alternate blinking during alarms
LED 1 blinks M times, and then LED 2 blinks N times.
The cycle then repeats.
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm
N = Alarm No.
* Refer to “Examples of alarm display” below.
Insufficient gas indicator
Refrigerant recovery mode
Automatic address setting
Automatic address setting in progress
Automatic address setting alarm (E15)
Automatic address setting alarm (E20)
Automatic address setting alarm (Other than E15 and E20)
(0.25/0.75)
(0.75/0.25)
(0.25/0.75)
(0.75/0.25)
Blinking alternately
Blinking simultaneously
Blinking simultaneously
Blinking simultaneously
:ON
:Blinking (0.25/0.75) indicates that the lamp illuminates for 0.25 seconds, and then is OFF for 0.75 seconds.
Unless otherwise indicated, the blinking is (0.5/0.5).
:OFF
Examples of alarm display (other than E15, E16, and E20)
Alarm / Display
LED 1 Alternately LED 2
P02
( Blinks 2 times )
(Blinks 2 times)
P03
( " )
(Blinks 3 times)
P04
( " )
(Blinks 4 times)
P05
( " )
(Blinks 5 times)
P31
( " )
(Blinks 31 times)
H01
(Blinks 3 times)
(Blinks 1 times)
H02
( " )
(Blinks 2 times)
H03
( " )
(Blinks 3 times)
•
•
E04
(Blinks 4 times)
(Blinks 4 times)
•
•
F07
(Blinks 5 times)
(Blinks 7 times)
•
•
L13
(Blinks 6 times)
(Blinks 13 times)
•
•
Note:
This table shows examples of alarms.
Other type of alarms may also be displayed.
SM830194-04_Single_BigPAC.indb 4
2014/11/13 18:18:54
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...