E-023-2-E
Flowmeter
Transmitter
OVAL Coriolis Flowmeter
Receiving Instrument
(Load R
L
built in)
Connection
Points
PC
Interface
Application Software
(LinkTop)
Probe
Polarity observation not required.
Connect probe a and - terminals
of analog output.
Tie-point
Terminal Block
LINE/
+
NEUT/
−
LINE/
+
Power
R
L
NEUT/
−
+
4
〜
20mADC
−
+
−
Fig.2
2.2 Hookup with Associated Equipment and Devices
Equipment set-up with associated equipment and devices are shown in Fig. 2.
NOTE: In Fig. 2, the customer is to supply the PC that meets the following requirements:
◇
PC/AT compatible (DOS/V machine)
◇
Operating system is the Windows 2000, Windows XP, Windows Vista, Windows 7.
◇
RAM: 8MB or larger.
◇
Hard disk: 10MB or larger
◇
Provision of USB port
The receiving instrument in the figure above requires a load resistance 250Ω min. Its upper limit depends
on the specification of transmitter used.
If the receiving instrument does not have a built-in R
L
, use it with an external R
L
connected in series.