3-17
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
o1-02
Power-On
Monitor
1 to 4
---
1
Basic or Advanced
The following example shows how to change parameter o1-02 so that the output current is displayed at
startup. (The procedure continues from the end of the previous example.)
Key sequence
Display
Explanation
User Monitor Sel
Output kWatts
Monitor Select display (See the previous example.)
Power-On Monitor
Frequency Ref
Displays the Power-On Monitor display.
o1-02= 1 ***
Frequency Ref
Displays the parameter setting for o1-02.
2 times
O1-02= 3
Output Current
Sets the parameter to output current.
Entry Accepted
Writes the new setting.
Power-On Monitor
Output Current
Returns to the Power-On Monitor display.
Function o1
Monitor Select
Returns to the function selection o1 display.
** Main Menu **
Programming
Returns to the program mode display.
Note In this example, the setting is changed in the Basic access level.
Preparing for Operation
Chapter 3
Содержание SYSDRIVE 3G3FV
Страница 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Страница 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Страница 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Страница 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Страница 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Страница 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Страница 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...