6-79
Function(s)
Setting(s)
Page
3-Wire Control (with forward/reverse rotation input)
0
5-16
Multi-step References 1 through 3 and Jog Reference
3 through 6 5-17
Multi-Accel/Decel 1 and 2 (acceleration/deceleration time selectors 1 and 2)
7 and 1A
5-18
Fast-Stop (Emergency stop)
15 and 17
5-19
Forward and Reverse Jog commands
12 and 13
5-19
Terminal 13/14 Switch
1F
5-19
Timer Function Input
18
6-46
Energy-saving operation
63
6-13,
6-37
Two-motor switching control
16
6-67
PID control integral reset
30
6-54
PID control integral hold
31
6-54
D
Local/Remote Selection (Setting: 1)
OFF
Operate with the frequency reference and run command specified in b1-01 (the frequency
reference source selector) and b1-02 (the run command source selector).
ON
Operate with the frequency reference and run command set at the Digital Operator.
•
With this setting, the multi-function input selects the input method for the frequency reference and run
command.
•
The input method can be switched only when the Inverter is stopped.
•
The Digital Operator’s LOCAL/REMOTE Key is disabled when this function has been set in a multi-
function input.
Note 1. There is no difference between two modes if the parameters b1-01 and b1-02 are both set to
0.
Note 2. The above values are set through the Digital Operator and the frequencies are stored in fre-
quency references 1 through 8 (d1-01 through d1-08) or the inching frequency reference
(d1-09) in remote or local mode.
Note 3. Multi-function inputs 1 through 6 are enabled in remote or local mode. The stop command is,
however, disabled in local mode only if the 3-wire sequential set value is 0.
Note 4. If the run command is input when switching the Inverter to remote mode from local mode, the
run input will be ignored to ensure safety. Turn the run command OFF once. Then turn the run
command ON again in remote mode. If the parameter b1-07 (LOC/REM RUN Sel) is set to 1,
the run command will not be ignored. In this case, the Inverter may operate immediately when
switched to remote mode from local mode. Take necessary measures for safety.
D
Option/Inverter Selection (Setting: 2)
OFF
The Inverter’s frequency reference is enabled.
ON
The Optional Card’s frequency reference is enabled.
•
With this setting, the multi-function input enables the frequency reference input from the Inverter itself
or the one from Optional Card.
•
The frequency reference input can be switched only when the Inverter is stopped.
•
Be sure that b1-01 (the frequency reference source selector) has been set to 0 (Operator) or 1 (exter-
nal terminal). Only the frequency reference from the Optional Card will be enabled if b1-01 is set to 3
(Option PCB).
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3FV
Страница 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Страница 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Страница 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Страница 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Страница 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Страница 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Страница 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...