6-101
Parameter
Display name
Setting
Units
Default
Valid access levels
*2
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L3-01
StallP Accel Sel
0 to 2
---
1
Basic or Advanced
N.A.
Note 1. This parameter cannot be changed during operation.
Note 2. N.A. = Not applicable.
Setting
Function
0
Disabled. (Accelerate according to the settings. Stalls may occur with large loads.)
1
Enabled. (Stop acceleration if L3-02 setting is exceeded. Accelerate again when current recovers.)
2
Intelligent. (Adjust acceleration so that the L3-02 isn’t exceeded by much. Ignore the acceleration
time setting.)
•
When setting 1 (enabled) is selected, acceleration is stopped if the motor current exceeds the accel-
eration stall prevention level. Acceleration is started again when the current falls below this level.
•
When setting 2 (intelligent) is selected, acceleration is performed using the the acceleration stall pre-
vention level as a basis. In this case, the acceleration time is ignored.
Parameter
Display name
Setting
Units
Default
Valid access levels
*2
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L3-02
StallP Accel Lvl
0 to 200
%
150
Basic or Advanced
N.A.
Note 1. This parameter cannot be changed during operation.
Note 2. N.A. = Not applicable.
•
This setting is valid when L3-01 is set to 1 or 2.
•
There is normally no need to change this setting.
•
Decrease this setting when the motor’s capacity is small compared to the Inverter’s capacity or stalling
occurs when the motor is operated with the default setting. The standard target setting is 2 to 3 times
the motor’s rated current. (Set this current value as a percentage of the Inverter’s rated current, i.e.,
100% corresponds to the Inverter’s rated current.)
Acceleration Stall Prevention Example: L3-01 = 1
Output current
Output frequency
L3-02 (Acceleration stall prevention level)
The output frequency is controlled
to prevent stalling.
Time
Time
Parameter
Display name
Setting
Units
Default
*2
Valid access levels
*3
number
p y
g
range
setting
*2
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L3-03
StallP CHP Lvl
0 to 100
%
50
Advanced
N.A.
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3FV
Страница 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Страница 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Страница 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Страница 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Страница 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Страница 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Страница 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...