3-23
The following restrictions apply to setting/displaying parameters when the access level is set to the user
level.
Mode
Accessible parameters
Operation
The Quick-start level parameters can be displayed.
Initialize
The Quick-start level parameters can be set or displayed.
Program
Only the parameters specified in A2-01 through A2-32 can be set or displayed.
Auto-tuning
The parameters cannot be displayed.
Modified constants
The parameters cannot be displayed.
Setting Example
The following example shows how to specify parameter C1-01 (Acceleration time 1) in user parameter
A2-01 and set the access level to the user level.
Key sequence
Display
Explanation
** Main Menu **
Operation
Displays operation mode.
** Main Menu **
Initialize
Displays initialize mode.
Select Language
English
Puts the Unit in initialize mode.
(Select Language display)
Function A2
User Parameters
Displays the User Parameters display.
User Param 1
A2-01= -----
Displays the parameter setting for A2-01.
User Param 1
-----
Selects the parameter so that the leading digit flashes.
(The digit that can be changed flashes.)
2 times
User Param 1
C1-01
Sets the first digit to “C.”
(At this point the other digits will be displayed.)
2 times
User Param 1
C1-01
Moves the cursor to the third digit.
7 times
User Param 1
C1-08
Sets the last digits to “08.”
Entry Accepted
Writes the new setting.
User Param 1
A2-01= C1-08
Returns to the parameter setting for A2-01.
Function A2
User Parameters
Returns to the User Parameters display.
2 times
Access Level
Advanced Level
Displays the Access Level display.
A1-01= 4
ADVANCED
Displays the parameter setting for A1-01.
2 times
A1-01= 1
User Level
Changes the setting to “User Level.”
Entry Accepted
Writes the new setting.
Access Level
User Level
Returns to the Access Level display.
** Main Menu **
Initialize
Returns to the initialize mode display.
Preparing for Operation
Chapter 3
Содержание SYSDRIVE 3G3FV
Страница 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Страница 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Страница 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Страница 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Страница 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Страница 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Страница 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...