6-36
6-4
V/f Control With PG Feedback
This section summarizes the functions that can be used with V/f control with PG feed-
back, and provides detailed explanations of the functions that are specific to V/f control
with PG feedback.
6-4-1 Summary of V/f Control With PG Feedback Functions
An “OK” in the control mode column indicates that the parameter can be changed in that control mode.
The functions specific to V/f control with PG feedback are marked with a “
S
” and described in more
detail later in this section.
Group
Function
Control mode
G oup
u c o
V/f
V/f
w/PG
Open-loop
Vector
Flux
Vector
Application
b1
Sequence
Settings such as the reference input method
OK
OK
OK
OK
ca o
b2
DC Braking
DC braking function settings
OK
OK
OK
OK
b3
Speed Search
Speed search function settings
OK
OK
OK
OK
b4
Delay Timers
Timer function settings
OK
OK
OK
OK
b5
PID Control
PID control settings
OK
OK
OK
OK
b6
Reference Hold
Accel/deceleration time dwell function settings
OK
OK
OK
OK
b7
Droop Control
Not used. (Can’t be set.)
---
---
---
OK
b8
Energy Saving
S
Multi-function input: Sets energy-saving control
by energy saving reference.
OK
OK
---
---
b9
Zero Servo
Not used. (Can’t be set.)
---
---
---
OK
Tuning
C1
Accel/Decel
Acceleration/deceleration time settings
OK
OK
OK
OK
u
g
C2
S-Curve Acc/Dec
S-curve characteristics for accel/decel times
OK
OK
OK
OK
C3
Motor-Slip Comp
Slip compensation function settings
OK
OK
OK
OK
C4
Torque Comp
Torque compensation function settings
OK
OK
OK
---
C5
ASR Tuning
Speed control adjustment
---
OK
---
OK
C6
Carrier Freq
Carrier frequency settings
OK
OK
OK
OK
C7
Hunting Prev
S
Hunting prevention settings
OK
OK
---
---
C8
Factory Tuning
Not used. (Can’t be set.)
---
---
OK
---
Reference
d1
Preset Reference
Frequency reference settings (when using Operator)
OK
OK
OK
OK
e e e ce
d2
Reference Limits
Frequency upper and lower limit settings
OK
OK
OK
OK
d3
Jump Frequencies
Prohibited frequency settings
OK
OK
OK
OK
d4
Sequence
Up/Down, Accel/Decel stop hold frequency setting
OK
OK
OK
OK
d5
Torque Control
Not used. (Can’t be set.)
---
---
---
OK
Motor
E1
V/f Pattern
S
Motor parameters
(M t
t
t
ll )
OK
OK
OK
OK
o o
E2
Motor Setup
S
o o
a a e e s
(Motor parameters are set manually.)
OK
OK
OK
OK
E3
Control Method 2
Control mode settings for second motor
OK
OK
OK
OK
E4
V/f Pattern 2
Parameter settings for second motor
OK
OK
OK
OK
E5
Motor Setup 2
a a e e se
gs o seco d
o o
OK
OK
OK
OK
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3FV
Страница 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Страница 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Страница 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Страница 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Страница 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Страница 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Страница 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...