6-2-4 Setting Motor Parameters
The motor parameters other than the V/f pattern parameters are described below:
Calculate the rated slip (E2-02) from the value shown on the motor’s nameplate with the following equa-
tion and set this value.
Rated slip = rated frequency (Hz) – rated speed (r/min)
×
number of poles/120
Set the no-load current (E2-03) at the rated voltage and rated frequency. Normally this value isn’t shown
on the motor’s nameplate, so it might be necessary to contact the motor manufacturer.
Parameter
Display name
Setting range Units
Default
Valid access levels
number
p y
g
g
setting*
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-02
Motor Rated Slip
0.00 to 20.00
Hz
2.90
Advanced
Quick Start, Basic,
E2-03
No-Load Current
0.00 to 2.90
(see note 2)
A
1.20
,
,
or Advanced
Note 1. The default setting depends upon the type of Inverter.
(The table shows the default settings for 200-V class, 0.4-kW Inverters.)
Note 2. The setting range is between 0.00 and 0.1 less than the Inverter’s rated current.
Note 3. These settings are used as reference values for the motor slip compensation function.
Set the motor’s terminal resistance (phase to phase) in parameter E2-05. Normally this value isn’t
shown on the motor’s nameplate, so it might be necessary to contact the motor manufacturer.
Parameter
Display name
Setting range
Units Default
Valid access levels
number
p y
g
g
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-05
Term Resistance 0.000 to 65.000
Ω
9.842
Advanced
Note 1. The default setting depends upon the type of Inverter.
(The table shows the default settings for 200-V class, 0.4-kW Inverters.)
Note 2. This setting is used as a reference value for the torque compensation function.
Parameter
Display name
Setting range Units
Default
Valid access levels
number
p y
g
g
setting*
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-10
Tcomp Iron Loss
0 to 65535
W
14
Advanced
---
Note 1. The default setting varies with the Inverter’s capacity. The above setting applies to 200-V
class, 0.4-kW Inverters.
Note 2. Set the motor iron core loss in 1-W increments. The default setting does not normally need to
be changed.
Note 3. The set value is used as the reference value for the torque compensation function.
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3FV
Страница 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Страница 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Страница 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Страница 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Страница 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Страница 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Страница 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...