Communications
Switch
1-3
Section
CPM2C Changes in SW2
22
Operation Previous CPU Units
The following instructions apply to CPU Units with lot numbers of 3180O (August
2000) or earlier.
The previous CPU Units do not detect a Programming Console connected to the
peripheral port, and SW2 of the DIP switch was used to set either “Programming
Console” or “Other device.”
SW2 Setting
Setting
Meaning
OFF
Programming Console connected to peripheral port.
ON
Device other than Programming Console connected to peripheral port.
SW1 Setting
Setting
Meaning
OFF
Use PC Setup settings for RS-232C port (DM 6645 to DM 6649).
ON
Use default settings for RS-232C port.
The relationship between the PC Setup settings, the setting of SW2, and the
startup operating mode for previous CPU Units is shown in the following table.
PC Setup
CPM2C Operating Mode
Address
Bits
Setting
p
g
DM6600
08 to 15
00 Hex
According to communications switch SW2 and peripheral port device.
Peripheral device
SW2 setting
p
OFF
ON
Nothing connected
PROGRAM mode
RUN mode
Programming
Console
According to Programming
Console key switch.
PROGRAM mode
(See note.)
Other
PROGRAM mode
(See note.)
PROGRAM mode
Note:
Communications will not be possible between the CPM2C and the
peripheral device for these combinations.
01 Hex
Mode used immediately before power interruption
02 Hex
Mode specified in bits 00 to 07.
00 to 07
00 Hex
PROGRAM mode
01 Hex
MONITOR mode
02 Hex
RUN mode
Note
1. The default setting for DM 6600, bits 06 to 15 is 00 Hex, i.e., according to the
communications switch on the front panel. If SW2 is set for connecting a de-
vice other than a Programming Console to the peripheral connector, the
CPU Unit will start in RUN mode as soon as power is turned ON. Be sure that
adequate precautions are taken to ensure safety.
2. If SW2 is for connecting a device other than a Programming Console to the
peripheral connector, the CPU Unit will start in RUN mode as soon as power
is turned ON even it a device is connected to the RS-232C port. Be sure that
adequate precautions are taken to ensure safety.
Содержание SRM1 - PROGRAMING 02-2001
Страница 1: ...Programmable Controllers Cat No W353 E1 06 SYSMAC CPM1 CPM1A CPM2A CPM2C SRM1 V2 PROGRAMMING MANUAL ...
Страница 2: ...CPM1 CPM1A CPM2A CPM2C SRM1 V2 Programmable Controllers Programming Manual Revised February 2008 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x ...
Страница 15: ...xvi ...