2-5
Section
CPM2A/CPM2C Pulse Output Functions
101
2-5-1 Using Single-phase Pulse Outputs Without Acceleration and
Deceleration (Fixed Duty Ratio)
Select the pulse output number.
Pulse output number 0 or 1
Wire the outputs.
Output numbers: 01000 and 01001
PC Setup (DM 6629)
PV coordinate system for pulse output numbers 0 and 1
Create a ladder diagram program.
PULS(65): For setting the number of output pulses.
SPED(64): For pulse output control without acceleration and deceleration.
INI(61): For stopping pulse outputs and changing the pulse output PV.
PRV(62): For reading the pulse output PV and status.
Single-phase Pulse Outputs
PULS(65)
SET
PULSES
instruction
SPED(64)
SPEED
OUTPUT
instruction
Pulse output 0
Pulse output 1
Specify relative or
absolute pulses.
Pulse output SV
(8 digits BCD)
INI(61)
MODE
CONTROL
instruction
Stop pulse outputs.
Change pulse output PV.
PC Setup
DM 6629,
bits 04 to 07
Output mode: Continuous or
Independent
Target frequency: 10 Hz to 10 kHz
Start pulse outputs.
Every scan
Every scan
Immediately
Pulse output status
AR 11
AR 12
Pulse output PV
SR 228
SR 229
SR 230
SR 231
PRV(62)
HIGH-SPEED COUNTER
PV READ instruction
Read pulse output PV.
Read pulse output
status.
Select either pulse number 0 or 1.
Output number
Pulse output number
01000
0
01001
1
Selecting the Pulse
Output Number