4-2
Section
CPM1/CPM1A Communications Functions
229
CPM1A PCs
OMRON Programmable Terminal
RS-232C Cable
CPM1A CPU Unit
RS-232C
Adapter
PC Setup Settings
The settings relating to 1:1 NT Link PC communications must be set as shown in
the following table.
Word
Bit
Function
Setting
DM 6650
00 to 07
Port settings
1
00: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps)
01: Settings in DM 6651
00
(Any val-
ue is OK)
08 to 11
Link area for 1:1 PC Link via peripheral port
0: LR 00 to LR 15
0
(Any val-
ue is OK)
12 to 15
Communications mode
1
0: Host Link; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link
4
Note
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be
turned ON, and the default setting (0 or 00) will be used.
2. For information on the NT Link settings for another OMRON PC, refer to that
PC’s Operation Manual.
3. If an out-of-range value is set, the following communications conditions will
result. In that case, reset the value so that it is within the permissible range.
Communications mode:
Host Link
Communications format:
Standard settings
(1 start bit, 7-bit data; 2 stop bits, even parity,
9,600 bps)
Transmission delay:
No
Node number:
00
4-2-3 One-to-one PC Link Communications
In a 1:1 PC Link, a CPM1/CPM1A is linked to another CPM1/CPM1A, CPM2A/
CPM2C, CQM1, C200HX/HG/HE, or C200HS PC through an RS-232C Adapter
and standard RS-232C cable. One of the PCs will serve as the Master and the
other as the Slave. The 1:1 PC Link can connect up to 256 bits (LR 0000 to LR
1515) in the two PCs.