3-2
Section
Temperature Sensor Units
207
02000
CMP (20)
001
#7FFE
Detects completion of initialization.
ON when initialization complete.
01000
CMP (20)
001
#7FFF
02000
25506(=)
Detects an open-circuit alarm.
ON when an open-circuit alarm has been detected.
Programming with SCL2(––) Instruction (CPM2A/CPM2C Only)
Execution condition
MOV (21)
#0000
DM0001
25506(=)
SCL2 (–)
001
DM0010
DM0000
25506(=)
MOV (21)
#0001
DM0001
25504(CY)
25504(CY)
Parameter settings for data conversion:
DM0010
DM0011
DM0012
#0000
#0001
#0001
25313
(Always ON Flag)
When the converted value is non-negative,
stores #0000 in DM 0001.
When the converted value is negative, stores
#0001 in DM 0001.
Offset
∆
X (Hex)
∆
Y (BCD)
Operation
16
3
16
2
16
1
16
0
IR 001
10
3
10
2
10
1
10
0
Binary to BCD conversion
DM 0000
1/0
1: Negative, 0: Non-negative
0: If data non-negative, “0000” stored in DM 0001
1: If data negative, “0001” stored in DM 0001
0
0
0
1/0
DM 0001
CY (when using SCL2 instruction)