1-1
Section
PC Setup
12
Word(s)
Page
Function
Bit(s)
DM 6654
00 to 07
Start code (00 to FF)
(This setting is valid only when bits 8 to 11 of DM 6648 are set to 1.)
226
08 to 15
When bits 12 to 15 of DM 6648 set to 0:
Sets the number of bytes to receive. (00: 256 bytes; 01 to FF: 1 to 255 bytes)
When bits 12 to 15 of DM 6648 set to 1:
Sets the end code. (00 to FF)
Error Log Settings (DM 6655)
The following settings are effective after transfer to the PC.
DM 6655
00 to 03
Style
0: Shift after 7 records have been stored
1: Store only first 7 records (no shifting)
2 to F: Do not store records
21
04 to 07
Not used.
08 to 11
Cycle time monitor enable
0: Generate a non-fatal error for a cycle time that is too long.
1: Do not generate a non-fatal error.
12 to 15
Low battery error enable
0: Generate a non-fatal error for low battery voltage.
1: Do not generate a non-fatal error.
Low battery error detection is disabled (i.e., set to 1) by default in CPU Units that do
not have a clock. If the PC Setup is cleared, the setting will changed to 0 and a low
battery error will occur.
Bits 12 to 15 should always be set to 0 when the optional CPM2C-BAT01 is mounted.