2-7
Section
Synchronized Pulse Control (CPM2A/CPM2C Only)
137
Select the differential phase input mode, the pulse + direction input mode, the
up/down pulse input mode, or the increment mode. These modes are explained
below.
Select one of the following as the input frequency range: 10 Hz to 500 Hz, 20 Hz
to 1 kHz, or 300 Hz to 20 kHz. For more information on input frequencies, refer to
the following diagrams.
Differential Phase Input Mode
In the differential phase input mode, the count is incremented or decremented
according to two differential phase signals (phase A and phase B) with a multi-
plication factor of 4.
Phase A
Phase B
Nms
→
Frequency =
1,000
N
ON
OFF
ON
OFF
Pulse + Direction Input Mode
In the pulse + direction input mode, pulse signals and direction signals are input,
and the count is incremented or decremented according to the direction signal
status.
Nms
→
Frequency =
1,000
N
Pulse inputs
Direction
inputs
ON
OFF
ON
OFF
Up/Down Pulse Input Mode
In the up/down pulse input mode, CW signals (up pulses) and CCW signals
(down pulses) are input, and the count is incremented or decremented accord-
ingly.
Nms
→
Frequency =
1,000
N
CW inputs
CWW inputs
Incremented
Decremented
ON
OFF
ON
OFF
Selecting the Input Mode
Selecting the Pulse
Synchronization Input
Frequency
Содержание SRM1 - PROGRAMING 02-2001
Страница 1: ...Programmable Controllers Cat No W353 E1 06 SYSMAC CPM1 CPM1A CPM2A CPM2C SRM1 V2 PROGRAMMING MANUAL ...
Страница 2: ...CPM1 CPM1A CPM2A CPM2C SRM1 V2 Programmable Controllers Programming Manual Revised February 2008 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x ...
Страница 15: ...xvi ...