3-2
Section
Temperature Sensor Units
197
cluding the Temperature Sensor Units.) Up to three Units can be connected to
the CPM2C-S. No matter how many Units are connected, however, no more
than 0 input words and 10 output words can be allocated in one PC. There are no
restrictions on the order in which Units can be connected.
CPM2C CPU Unit
Expansion I/O Unit
CPM2C-TS001/101
Temperature Sensor Units
Four Temperature
Sensor Units max.
Example
Word Allocation
Words are allocated to Temperature Sensor Units just like other Expansion I/O
Units and Expansion Units: In the order in which the Units are connected. A
CPM2C-TS001 or CPM2C-TS101 Temperature Sensor Unit will thus be allo-
cated the next two input words after the Unit to which it is connected (CPU Unit or
other Unit). No output words are allocated.
20-point CPU Unit
Inputs
IR 000
Outputs
IR 010
CPM2C-TS001
Temperature
Sensor Unit
CPM2C-TS001
Temperature
Sensor Unit
CPM2C-TS101
Temperature
Sensor Unit
CPM2C-TS101
Temperature
Sensor Unit
CPM2C-24EDTC
Expansion I/O Unit
Inputs
IR 009
Outputs
IR 011
Inputs
IR 001
IR 002
Outputs
None
Inputs
IR 005
IR 006
Outputs
None
Inputs
IR 007
IR 008
Outputs
None
Inputs
IR 003
IR 004
Outputs
None
3-2-5 Setting Temperature Ranges
The temperature unit, the number of decimal places used, and the temperature
input range are set on the DIP switch and rotary switch on the Temperature Sen-
sor Unit.
Note
1. Always turn OFF the power supply before setting the temperature range.
2. Never touch the DIP switch or rotary switch during Temperature Sensor Unit
operation. Static electricity may cause operating errors.