CPM2A/CPM2C Communications Functions
244
CPM2C DIP Switch Settings
When SW2 is set to OFF, communications through the peripheral port are set to
Programming Console protocol, regardless of the setting of pin 1 or the settings
in the PC Setup.
Front View
CPU Unit with Relay Out-
puts via Terminal Block
CPU Unit with Transistor Outputs
via Fujitsu-compatible Connector
CPU Unit with Transistor Outputs
via MIL Connector
2. Input terminals
7. Communications port
8. Communications switch
9. Customize switch
5. Input indicators
6. Output indicators
3. Output terminals
4. Status indicators
2. Input connector
3. Output connector
7. Communications port
8. Communications switch
9. Customize switch
5. Input indicators
6. Output indicators
4. Status indicators
2. Input connector
3. Output connector
DIP switch for Units
with 10/20 I/O points
(8)
(9)
(8)
(9)
DIP switch for Units
with 32 I/O points
When SW 2 is set to ON, the status of SW 1 determines whether communica-
tions through the peripheral port and RS-232C port are governed by the settings
in the PC Setup or the standard settings (1 start bit, 7 data bits, 2 stop bits, even
parity, and 9,600 bps baud rate).
SW1
Communications settings
OFF
The communications settings for the peripheral port and RS-232C
port will be determined by the settings in the PC Setup (DM 6645 to
DM 6649, DM 6650 to DM 6654). If a Programming Console is
connected to the peripheral port, however, operation for that port will
be in the Programming Console mode.
ON
The communications settings for the peripheral port and RS-232C
port will be the standard settings. If a Programming Console is
connected to the peripheral port, however, operation for that port will
be in the Programming Console mode.
An RS-232C Adapter is needed to perform Host Link communications from a
peripheral port.
Note
When performing host link communications via the peripheral port of a CPU Unit
with a manufacturing number of 3180O or earlier (i.e., manufactured on or
before April 31, 2000), set SW2 to ON. See above for details of the settings of
SW2. When using a CPU Unit with a manufacturing number of 3180O or earlier
(i.e., manufactured on or before April 31, 2000), do not change the setting of
SW2 with a Programming Console, the CPM2C-CIF01-V1/11, or the
CQM1-CIF01/02 connected. If the setting of SW2 is changed in this state, com-
munications will be interrupted, and a communications error will be generated or
the Programming Console will enter a “no-response” state (i.e., pressing the
keys of the Programming Console will have no effect and the display will stay the
same).