5-3 Safety I/O Terminal with Relay Outputs
5-12
WARNING
For Model DST1-MRD08SL-1, Apply only one AC line phase to the relays
output.
L1 L2 L3 N
DST1-
MRD08SL-1
L1 L2 L3 N
DST1-
MRD08SL-1
Fuse
Fuse
Load
Load
Load
Load
Correct
Incorrect
For Model DST1-MRD08SL-1, Insert a fuse rated at 3.15A or less for each
output terminal to protect safety output contacts from welding.
Confirm the fuse selection with the fuse manufacturer to ensure the
dependability of the characteristics of the connected load.
IMPORTANT
•
Supply power to both V0 and V1. The states of the relay contacts are
internally monitored from the power supply of V 0.
•
Power supply terminal V1 for the outputs is internally monitored. Supply
the voltage in the specified range (20.4 to 26.4 VDC). If the voltage is
supplied outside this range, voltage will not be supplied to the output
circuits.
5-3-6 Dimensions
The following figures show the dimensions of the DST1-MRD08SL-1 (unit: mm).
(94.7)
90
35.5
63
83.2
170
Содержание DST1 Series
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ...DST1 series Safety I O Terminals Operation Manual Produced April 2005 ...
Страница 6: ......
Страница 24: ...Section 1 Overview ...
Страница 44: ...Section 2 General Procedure ...
Страница 50: ...Section 3 Configuration ...
Страница 63: ...Section 4 Specifications ...
Страница 67: ...Section 5 DST1 series ...
Страница 79: ...Section 6 Troubleshooting and Maintenance ...
Страница 87: ...Section 7 Wiring Examples ...
Страница 97: ...Appendices ...
Страница 114: ...Cat No Z904 E1 01 OPERATION MANUAL DST1 series Safety I O Terminals ...