5-3 Safety I/O Terminal with Relay Outputs
The following table shows the terminal arrangement of the terminal blocks on the DST1-MRD08SL-1.
Terminals Names
Functions
1, 2
V0
11, 12
G0
Power terminals for the input devices, test outputs and internal relay
feedback monitors.(24VDC)
17 to 20
G0
Common terminals. Terminals 11, 12, and 17 to 20 are internally
connected.
3 to 6
IN0 to IN3
Terminals for safety inputs
7 to 10
13 to 16
T0 to T3
Terminals for test/standard outputs
21, 22
V1
31, 32
G1
Power terminals for driving internal relays.(24VDC)
23 to 30
33 to 40
OUT0 to OUT3
C0 to C3
OUT0e to OUT3e
C0e to C3e
Terminals for safety outputs
Outputs of terminals 23/33 (OUT0) and 24/34 (OUT0e) are the same.
Output of terminals 25/35 (OUT1) and 26/36 (OUT1e) are the same.
Output of terminals 27/37 (OUT2) and 28/38 (OUT2e) are the same.
Output of terminals 29/39 (OUT3) and 30/40 (OUT3e) are the same.
I/O Power Supply
Circuit
Internal
Circuit
Test Output Circuit
V0
V0+
G0
T0...T3
Safety Input Circuit
IN0...IN3
I/O Power Supply
Circuit
Safety Output Circuit
V1
V1+
G1
OUT0
...OUT3
X
C0...C3
OUT0e
…OUT3e
C0e...C3e
V0+
5-11
Содержание DST1 Series
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ...DST1 series Safety I O Terminals Operation Manual Produced April 2005 ...
Страница 6: ......
Страница 24: ...Section 1 Overview ...
Страница 44: ...Section 2 General Procedure ...
Страница 50: ...Section 3 Configuration ...
Страница 63: ...Section 4 Specifications ...
Страница 67: ...Section 5 DST1 series ...
Страница 79: ...Section 6 Troubleshooting and Maintenance ...
Страница 87: ...Section 7 Wiring Examples ...
Страница 97: ...Appendices ...
Страница 114: ...Cat No Z904 E1 01 OPERATION MANUAL DST1 series Safety I O Terminals ...