Appendix 1: DeviceNet Explicit Messages
Setting and Monitoring a Safety Input
Command
Explicit
message
Read/
write
Function
Service
Code
Class
ID
Instance
ID
Attribute
ID
Data size
Response
Read Reads the monitor
mode for
maintenance
information of the
input (1 to 12)
specified by the
instance ID.
0E hex
3D
hex
01 to 0C
hex
65 hex
1 byte
00 hex: Total ON
time mode
01 hex: Contact
operation counter
mode
Terminal
Maintenance
Information
Monitor Mode
Write Writes the monitor
mode for
maintenance
information of the
input (1 to 12)
specified by the
instance ID.
10 hex
3D
hex
01 to 0C
hex
65 hex
1 byte
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
Read Reads the set value
for the total ON time
(unit: s) or number
of contact
operations (unit:
operations) of the
input (1 to 12)
specified by the
instance ID.
0E hex
3D
hex
01 to 0C
hex
68 hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
Input Set
Value for
Total ON
Time or
Contact
Operation
Counter
Write Writes the set value
for the total ON time
(unit: s) or number
of contact
operations (unit:
operations) of the
input (1 to 12)
specified by the
instance ID.
10 hex
3D
hex
01 to 0C
hex
68 hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
Input Total
ON Time or
Contact
Operation
Counter Read
Read Reads the set value
for the total ON time
(unit: s) or number
of contact
operations (unit:
operations) of the
input (1 to 12)
specified by the
instance ID.
0E hex
3D
hex
01 to 0C
hex
66 hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
Input Total
ON Time or
Contact
Operation
Counter
Reset
Reset Resets the total ON
time or number of
contact operations
(unit: operations)
for time input (1 to
32) specified by the
instance ID.
05 hex
3D
hex
01 to 0C
hex
66 hex
Input Monitor
Status for
Total ON
Time or
Contact
Operation
Counter Read
Read Reads the set value
for the total ON time
(unit: s) or number
of contact
operations (unit:
operations) of the
input (1 to 12)
specified by the
instance ID.
0E hex
3D
hex
01 to 0C
hex
67 hex
1 byte
00 hex: Within
range
01 hex: Over
range (over the
monitor value)
A-5
Содержание DST1 Series
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ...DST1 series Safety I O Terminals Operation Manual Produced April 2005 ...
Страница 6: ......
Страница 24: ...Section 1 Overview ...
Страница 44: ...Section 2 General Procedure ...
Страница 50: ...Section 3 Configuration ...
Страница 63: ...Section 4 Specifications ...
Страница 67: ...Section 5 DST1 series ...
Страница 79: ...Section 6 Troubleshooting and Maintenance ...
Страница 87: ...Section 7 Wiring Examples ...
Страница 97: ...Appendices ...
Страница 114: ...Cat No Z904 E1 01 OPERATION MANUAL DST1 series Safety I O Terminals ...