Appendix 1: DeviceNet Explicit Messages
A-1-2 Explicit
Messages
Reading General Status
Command
Explicit
message
Read/
write
Function
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Response
General
Status Read
Read Reads
the
specified slave’s
status flags (8 bits)
0E hex 95 hex 01 hex
65 hex
−
1 byte
Setting and Monitoring the Unit Conduction Time
Command
Explicit
message
Read/
write
Function
Service
Code
Class
ID
Instance
ID
Attribute
ID
Data size
Response
Read Reads the set
value for the Unit
Conduction Time
(unit: 0.1 h).
0E hex 95 hex 01 hex
73 hex
−
4 bytes
0000 0000 to FFFF
FFFF hex
(0 to
4,294,967,295)
Unit
Maintenance
Set Value
Write Writes the set
value
for the Unit
Conduction
Time (unit: 0.1 h).
10 hex 95 hex 01 hex
73 hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
Unit
Maintenance
Present
Value
Read Reads the present
value for the Unit
Conduction
Time (unit: 0.1 h).
0E hex 95 hex 01 hex
71 hex
4 bytes
0000 0000 to FFFF
FFFF hex
(0 to
4,294,967,295)
Unit
Maintenance
Flag
Read Reads the monitor
status of Unit
Conduction Time.
0E hex 95 hex 01 hex
72 hex
1 byte
00 hex: Within
range
01 hex: Over range
(over the monitor
value)
A-4
Содержание DST1 Series
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ...DST1 series Safety I O Terminals Operation Manual Produced April 2005 ...
Страница 6: ......
Страница 24: ...Section 1 Overview ...
Страница 44: ...Section 2 General Procedure ...
Страница 50: ...Section 3 Configuration ...
Страница 63: ...Section 4 Specifications ...
Страница 67: ...Section 5 DST1 series ...
Страница 79: ...Section 6 Troubleshooting and Maintenance ...
Страница 87: ...Section 7 Wiring Examples ...
Страница 97: ...Appendices ...
Страница 114: ...Cat No Z904 E1 01 OPERATION MANUAL DST1 series Safety I O Terminals ...