Appendix 1: DeviceNet Explicit Messages
Command
Explicit
message
Read/
write
Function
Service
Code
Class
ID
Instance
ID
Attribute
ID
Data size
Response
Safety Output
Cause of Error
Information
Read
Read Reads the cause for
the normal flag (1 to
8) specified by the
Instance ID turning
OFF.
0E hex
09
hex
01 to 04
hex
76 hex
0 = No error
01 hex: Con-
figuration invalid
02 hex: Overload
detected
05 hex:
Stuck-at-high
detected
06 hex:
Undercurrent
detected for
muting lamp
Setting and Monitoring Operation Time
Command
Explicit
message
Read/
write
Function
Service
Code
Class
ID
Instance
ID
Attribute
ID
Data size
Response
Read Reads the monitor
value for the time
(unit: ms) from
when the output (1
to 8) specified by
the instance ID
turns ON until the
corresponding input
turns ON.
0E hex
97
hex
01 to 10
hex
67 hex
−
2 bytes
0000 to FFFF hex
(0 to 65535)
Set Value for
Operation Time
Monitor
Write Writes the monitor
value for the time
(unit: ms) from
when the output (1
to 8) specified by
the instance ID
turns ON until the
corresponding input
turns ON.
10 hex
97
hex
01 to 10
hex
67 hex
2 bytes
0000 to
FFFF hex
(0 to 65535)
Present Value
for Operation
Time Monitor
Read Reads the present
value for the time
(unit: ms) from
when the output (1
to 8) specified by
the instance ID
turns ON until the
corresponding input
turns ON.
0E hex
97
hex
01 to 10
hex
65 hex
−
2 bytes
0000 to FFFF hex
(0 to 65535)
Monitor Status
Value for
Operation Time
Monitor Read
Read Reads the monitor
status for the time
(unit: ms) from
when the output (1
to 8) specified by
the instance ID
turns ON until the
corresponding input
turns ON.
0E hex
97
hex
01 to 10
hex
66 hex
−
1 byte
00 hex: Within
range
01 hex: Over
range (over the
monitor value)
A-9
Содержание DST1 Series
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ...DST1 series Safety I O Terminals Operation Manual Produced April 2005 ...
Страница 6: ......
Страница 24: ...Section 1 Overview ...
Страница 44: ...Section 2 General Procedure ...
Страница 50: ...Section 3 Configuration ...
Страница 63: ...Section 4 Specifications ...
Страница 67: ...Section 5 DST1 series ...
Страница 79: ...Section 6 Troubleshooting and Maintenance ...
Страница 87: ...Section 7 Wiring Examples ...
Страница 97: ...Appendices ...
Страница 114: ...Cat No Z904 E1 01 OPERATION MANUAL DST1 series Safety I O Terminals ...