– 569 –
CHAPTER 5
Operation Procedure for System with PIR
[Start]
STEP 1
TSW card to be replaced is in STBY mode?
Check TSW ACT lamp on the TSW card. When the lamp is off, the card is in STBY mode.
YES: Proceed to STEP 3.
NO: Changeover the ACT/STBY of speech path by using CMOD. Proceed to STEP 2.
STEP 2
Confirm the mate TSW has been placed in ACT mode.
When TSW ACT lamp lights green on the mate TSW card, changeover is successful.
STEP 3
Turn ON (upward) MBR key on the TSW to be replaced.
•
TSW ACT lamp lights red on the all TSW cards that are placed in STBY mode.
STEP 4
Turn ON (upward) MB key on the TSW to be replaced.
•
SYNC lamp goes OFF on all MUX cards that are under the TSW card whose MB key is set ON.
STEP 5
Extract the TSW card to be replaced.
STEP 6
Set the keys on the new TSW card, referring to the card replaced.
STEP 7
Turn ON (upward) MBR and MB keys on the new TSW card.
STEP 8
Insert the new TSW card.
•
TSW ACT lamp light red on the new TSW card.
STEP 9
Turn OFF (downward) MB key on the new TSW card.
•
TSW ACT lights red
•
M0SY/M1SY/M2SY/M3SY lamps light green
•
SYNC lamps light green on all MUX cards that are under the new TSW card.
STEP 10 Turn OFF (downward) MBR key on the new card.
•
TSW ACT lamp goes off on all TSW cards that are placed in STBY mode.
STEP 11 Change over the ACT/STBY of speech path by using CMOD command.
STEP 12 Make sure the following:
[ACT side]
•
TSW ACT lights green (TSW card)
•
OPE/MB lights green (DLKC card)
Содержание SV8500
Страница 303: ...256 CHAPTER 3 System Messages Related call release result b7 b0 b7 0 1 Released Not released 4...
Страница 376: ...329 CHAPTER 3 System Messages Level Level b7 b6 b5 b4 b3 b2 b1 b0 G0 G1 G2 G3 G30 G31 0 1 Ineffectively held...
Страница 378: ...331 CHAPTER 3 System Messages Level Level b7 b6 b5 b4 b3 b2 b1 b0 G0 G1 G2 G3 G30 G31 0 1 Ineffectively held...
Страница 547: ...500 CHAPTER 3 System Messages IP Address of when failed to LOGIN b7 b6 b5 b4 b3 b2 b1 b0 16 19...
Страница 597: ...550 CHAPTER 4 Fault Repair Procedures This page is for your notes...
Страница 728: ...681 CHAPTER 6 Routine Maintenance Procedure Condition And Cause Procedure and Parts Used...
Страница 748: ...701 CHAPTER 7 Maintenance Commands SYSTEM SELECT 3 SW 1 8 Not used STS OFF Fixed...
Страница 781: ...734 CHAPTER 7 Maintenance Commands Exit Exit the command Clear Clear the values Recalc Re calculate bandwidth data...
Страница 798: ...751 CHAPTER 7 Maintenance Commands Set Execute the assigned MW lamp control Exit Exit this command...
Страница 843: ...796 CHAPTER 7 Maintenance Commands Get Get the Individual Call Block Data Exit Exit this command...
Страница 973: ......
Страница 974: ...Printed in Japan 0901 020...
Страница 975: ......