– 742 –
CHAPTER 7
Maintenance Commands
Enter the IP address of SR-MGC, not the default IP address but the actual IP address to be allocated to the
target SR-MGC. In the case of two-unit SR-MGC, assign IP address of the SR T.
Mode:
The type of changeover and recovery is to be executed.
1 = Automatically switched to SR-MGC operation when communication failure has been detected be-
tween MGC and SR-MGC.
Automatically switched back to MGC operation when communication recovery has been detected be-
tween MGC and SR-MGC.
In FCCS Cluster network, if SR-MGC detects normality of communication between SR-MGC and
Primary node or SR-MGC and Backup nodes, SR-MGC will switch the rescued terminals back to the
recovered node.
2 = Automatically switched to SR-MGC operation when communication failure has been detected be-
tween MGC and SR-MGC.
Automatically switched back to MGC operation when communication recovery between MGC and
SR-MGC, and normality of communication between MGC and a selected terminal have been detect-
ed.
In FCCS Cluster network, if SR-MGC detects normality of communication between SR-MGC and
Primary node, Primary node and a selected terminal, SR-MGC will switch the rescued terminals back
to the Primary node.
3 = Not used.
C_MGC:
Select an Operating Mode for SR-MGC.
0 = Normal Operation
1 = Office data cannot be copied from the MGC when FCCS Cluster feature is used. This value must be
assigned to the Backup nodes used in FCCS Cluster network.
<Initialize Tab>
Initialization of SR-MGC can be activated on this tab.
Click either of the radio buttons and press the Execute button to execute initialization on the target SR-MGC.
All Initial:
Select this button to execute the initialization on all the SR-MGCs in the network (default setting).
Individual Initial:
Specify the SR-MGC Number when this button is selected.
<Change Operating Tab>
Содержание SV8500
Страница 303: ...256 CHAPTER 3 System Messages Related call release result b7 b0 b7 0 1 Released Not released 4...
Страница 376: ...329 CHAPTER 3 System Messages Level Level b7 b6 b5 b4 b3 b2 b1 b0 G0 G1 G2 G3 G30 G31 0 1 Ineffectively held...
Страница 378: ...331 CHAPTER 3 System Messages Level Level b7 b6 b5 b4 b3 b2 b1 b0 G0 G1 G2 G3 G30 G31 0 1 Ineffectively held...
Страница 547: ...500 CHAPTER 3 System Messages IP Address of when failed to LOGIN b7 b6 b5 b4 b3 b2 b1 b0 16 19...
Страница 597: ...550 CHAPTER 4 Fault Repair Procedures This page is for your notes...
Страница 728: ...681 CHAPTER 6 Routine Maintenance Procedure Condition And Cause Procedure and Parts Used...
Страница 748: ...701 CHAPTER 7 Maintenance Commands SYSTEM SELECT 3 SW 1 8 Not used STS OFF Fixed...
Страница 781: ...734 CHAPTER 7 Maintenance Commands Exit Exit the command Clear Clear the values Recalc Re calculate bandwidth data...
Страница 798: ...751 CHAPTER 7 Maintenance Commands Set Execute the assigned MW lamp control Exit Exit this command...
Страница 843: ...796 CHAPTER 7 Maintenance Commands Get Get the Individual Call Block Data Exit Exit this command...
Страница 973: ......
Страница 974: ...Printed in Japan 0901 020...
Страница 975: ......