6. System Diagnostic Tool
Scalable Modular Server DX2000 Maintenance Guide
33
Chapter 1 Maintenance
Operating the system diagnostic management tool
6.1.3
This section describes how to operate the system diagnostic management tool.
1.
Enter “list” in the Management Tool window and check that the power of server modules is turned off.
2.
Enter “start tedoli all” and start diagnosis for CSC modules/all loaded server modules.
3.
Enter “list” again after a few minutes. If Type of CPU Board is “TeDoLi” and Status is “Run”, CSC
modules/server modules have been diagnosed.
MNG PC> list
Module List Power Type Status
+----------------+----------+----------+----------+
CSC ON TP
CPU Board1 ON MNG PC
CPU Board2 OFF
CPU Board3 OFF
:
CPU Board43 OFF
CPU Board44 OFF
+----------------+----------+----------+----------+
CSC : 1 CPU : 43 + MNG PC
PASS: 0 PASS: 0
FAIL: 0 FAIL: 0
MNG PC>
MNG PC> start tedoli all
MNG PC>
MNG PC> list
Module List Power Type Status
+----------------+----------+----------+----------+
CSC ON TP Run
CPU Board1 ON MNG PC
CPU Board2 ON TeDoLi Run
CPU Board3 ON TeDoLi Run
:
CPU Board43 ON TeDoLi Run
CPU Board44 ON TeDoLi Run
+----------------+----------+----------+----------+
CSC : 1 CPU : 43 + MNG PC
PASS: 0 PASS: 0
FAIL: 0 FAIL: 0
MNG PC>