3. Error Messages of CSC Modules
Scalable Modular Server DX2000 Maintenance Guide
128
Chapter 3 Appendix
(2/3)
LCD display message
Cause
Solution
Baseboard Temperature2 Upper
Non-Critical
The sensor on the baseboard
detected the temperature over
the threshold.
Check the environment temperature and
the dust in the chassis. If you clean it and
find the problem, replace the PSU.
Contact a maintenance service
company.
Baseboard Temperature1 Upper
Non-Critical
The sensor on the baseboard
detected the temperature over
the threshold.
Baseboard Temperature Upper
Non-Critical
The sensor on the baseboard
detected the temperature over
the threshold.
Ambient Temperature Lower Non-Critical
The intake temperature of the
device is lower than the
threshold.
Check the environment temperature and
find no problem, replace the chassis.
Contact a maintenance service
company.
Ambient Temperature Upper Non-Critical
The intake temperature of the
device is higher than the
threshold.
BaseBoard Voltage Lower Non-Critical
The sensor on the baseboard
detected the voltage below the
threshold.
Replace the chassis. Contact a
maintenance service company.
BaseBoard Voltage Upper Non-Critical
The sensor on the baseboard
detected the voltage over the
threshold.
Processor2 Voltage Lower Non-Critical
The sensor of the CPU of on
LAN-SW#2 detected the
voltage below the threshold.
Replace the LAN-SW. Contact a
maintenance service company.
Processor2 Voltage Upper Non-Critical
The sensor of the CPU of on
LAN-SW#2 detected the
voltage over the threshold.
Sensor Failure Detected.
I2C internal bus error was
detected.
Contact a maintenance service
company.
Power Supply2 Temperature Lower
Critical
The temperature of PSU2 is
lower than the threshold.
Check the environment temperature and
find no problem, replace the PSU.
Contact a maintenance service
company.
Power Supply1 Temperature Lower
Critical
The temperature of PSU1 is
lower than the threshold.
Power Supply Temperature Lower Critical
The temperature of PSU3 is
lower than the threshold.
Power Supply2 Temperature Upper
Critical
The temperature of PSU2 is
higher than the threshold.
Check the environment temperature and
the dust in the chassis. If you clean it and
find the problem, replace the PSU.
Contact a maintenance service
company.
Power Supply1 Temperature Upper
Critical
The temperature of PSU1 is
higher than the threshold.
Power Supply Temperature Upper Critical
The temperature of PSU3 is
higher than the threshold.
Baseboard Temperature2 Lower Critical
The sensor on the baseboard
detected the temperature
below the threshold.
Check the environment temperature and
find no problem, replace the chassis.
Contact a maintenance service
company.
Baseboard Temperature1 Lower Critical
The sensor on the baseboard
detected the temperature
below the threshold.
Baseboard Temperature Lower Critical
The sensor on the baseboard
detected the temperature
below the threshold.
Baseboard Temperature2 Upper Critical
The sensor on the baseboard
detected the temperature
below the threshold.
Check the environment temperature and
the dust in the chassis. If you clean it and
find the problem, replace the chassis.
Contact a maintenance service
company.
Baseboard Temperature1 Upper Critical
The sensor on the baseboard
detected the temperature over
the threshold.
Baseboard Temperature Upper Critical
The sensor on the baseboard
detected the temperature over
the threshold.
Ambient Temperature Lower Critical
The intake temperature of the
device is lower than the
threshold.
Check the environment temperature and
find no problem, replace the chassis.
Contact a maintenance service
company.
Ambient Temperature Upper Critical
The intake temperature of the
device is higher than the
threshold.