Underground Corrosion Control
3:19
CP 1 – Cathodic Protection Tester Course Manual
©
NACE International, 2000
02/01/05
Figure 3.5 Cathodic Protection Rectifier Schematic
There are three basic types of rectifiers:
1.
Constant voltage — the DC voltage at the terminals remains constant
for all current outputs up to the rated maximum rectifier current.
2.
Constant current — the current output remains constant over a wide
range of circuit resistances up to the maximum rated output voltage.
3.
Constant potential — the current and voltage output vary to maintain a
pre-selected structure potential.
Where AC power is economically available, rectifiers have clear economic
and operating advantages over other power sources.
SOLAR PANELS
Solar panels generate DC by a photovoltaic action with sunlight. The panels
are combined with storage batteries to provide power during hours of
darkness and on cloudy days.