Installing C.P. Components
8:30
CP 1 – Cathodic Protection Tester Course Manual
©
NACE International, 2000
07/01/04
Some rectifiers don’t have transformers, but utilize solid state circuitry to
reduce the incoming power. These are called
switchmode rectifiers
.
AC Power and Wiring
AC wiring should be done by a licensed electrician. A fused switch box
should be installed ahead of the rectifier so power to the entire unit can be
turned off before any work is done on the rectifier.
Input voltage may vary from 480 volts to 115 volts. Both single phase and
three phase power is used, depending on rectifier requirements and
available power. Again, the AC wiring needs to be in the hands of a
qualified electrician. As an inspector, however, you will want to be sure the
unit is connected to the specified input voltage.
DC Output
Anode Circuit (Positive Circuit)
The portion of this circuit within the electrolyte has been discussed in detail
previously in the sections on various types of groundbeds. At the rectifier,
the anode cable is connected to the POSITIVE terminal, and the structure is
connected to the NEGATIVE terminal. Be certain that this connection is
made to the proper terminal.
Connecting a rectifier backward with the
structure cable connected to the rectifier positive terminal will lead to
rapid corrosion of the structure!
Above ground wiring should be installed in conduit. Where explosion-proof
installation is required, it is essential that all seals and other safety
equipment be properly installed. In such cases, it may be well to have the
above ground DC wiring done by a licensed electrician.
Negative Circuit
The
return
or
negative circuit
is the cabling from the structure to the
rectifier.
The underground or underwater portion of this wiring has been discussed
under “Impressed Current Groundbeds, Negative Circuit.” The above
ground portion is run, usually in conduit, to the rectifier negative terminal.
Follow all of the precautions mentioned previously under “Anode Circuit”
with regard to proper connection and installation.
Содержание CP 1
Страница 1: ...CP 1 Cathodic Protection Tester Course Manual February 2005 NACE International 2000 ...
Страница 265: ......
Страница 266: ......
Страница 267: ......
Страница 268: ......
Страница 301: ...RP0169 2002 32 NACE International ISBN 1 57590 035 1 ...
Страница 535: ...TM0101 2001 24 NACE International ISBN 1 57590 137 4 ...