3 Product description
Maschinenfabrik Reinhausen GmbH 2015
30
4349315/00 EN
VACUTAP® VR®
Function description
The protective relay is used to protect the on-load tap-changer and the
transformer when a malfunction occurs in the diverter switch oil compartment
or selector switch oil compartment. It is tripped when the specified speed of
oil flow from the on-load tap-changer head to the oil conservator is exceeded
due to a fault. The flowing oil actuates the flap valve which tips over into po-
sition OFF. The contact in the dry-reed magnetic switch is thereby actuated,
the circuit breakers are tripped, and the transformer is de-energized.
The protective relay is part of an oil-insulated on-load tap-changer and its
properties conform to IEC publication 60214-1 of the valid version. There-
fore, it is part of the scope of our delivery.
Diverter switch operations at rated switching capacity or at permissible over-
load will not cause the protective relay to trip.
The protective relay responds to oil flow, not to gas accumulated in the pro-
tective relay. It is not necessary to bleed the protective relay when filling the
transformer with oil. Gas accumulation in the protective relay is normal.
Performance features
The product is particularly characterized by the following properties:
▪
Vacuum resistance
▪
High temperature range
▪
Large electrical switching capacity range of the main switching contacts
▪
High insulation strength
▪
High dielectric strength to ground
3.4.1
3.4.2
Содержание VACUTAP VR
Страница 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Страница 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Страница 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Страница 266: ......
Страница 267: ......