12 Fault elimination
Maschinenfabrik Reinhausen GmbH 2015
227
4349315/00 EN
VACUTAP® VR®
5.
Check whether the pressure-operated relay sensor is in the OFF posi-
tion or OPERATION position.
Sensor in the OPERATION position
If the sensor is in the OPERATION position, there may be an error in the trip-
ping circuit. Check the tripping circuit in this case. If the cause for the pres-
sure-operated relay tripping cannot be ascertained this way, the diverter
switch insert or selector switch insert must be removed and checked in ac-
cordance with the corresponding operating instructions.
Sensor in the OFF position
Proceed as follows if the sensor is in the OFF position.
1.
Ensure that the transformer is not started up under any circumstances.
2.
Remove and inspect the diverter switch insert in accordance with corre-
sponding on-load tap-changer operating instructions.
3.
Contact and inform Maschinenfabrik Reinhausen of the following:
▪
What was the load of the transformer at the instant of tripping?
▪
Was there a tap-change operation on the on-load tap-changer immedi-
ately before or during the tripping?
▪
Did any other protective devices of the transformer respond at the in-
stant of tripping?
▪
Were switching operations in the network being carried out at the instant
of tripping?
▪
Were overvoltages registered at the instant of tripping?
▪
How high is the static pressure on the pressure relief device (height dif-
ference between the oil level in the on-load tap-changer oil conservator
and the pressure relief device)?
Re-commissioning the transformer
You can put the transformer back into operation after the cause for tripping
the pressure-operated relay has been determined and resolved:
1.
Ensure that the sensor on the snap-action switch is in the OPERATION
position.
2.
Commission the transformer.
12.2.1
12.2.2
12.2.3
Содержание VACUTAP VR
Страница 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Страница 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Страница 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Страница 266: ......
Страница 267: ......