6 Assembly: Bell-type tank design
Maschinenfabrik Reinhausen GmbH 2015
146
4349315/00 EN
VACUTAP® VR®
Lifting out diverter switch insert
1.
By turning the coupling tube on the upper screening ring, align it in such
a manner that the triangular marks on the on-load tap-changer head and
those on the coupling tube match up.
Figure 189: Aligning the coupling tube
2.
Insert the lifting gear in the eyebolts of the coupling tube and position
vertically above the diverter switch insert.
3.
Lift the diverter switch insert slowly and vertically out of oil compartment.
Figure 190: Diverter switch insert
4.
CAUTION!
Place the diverter switch insert on a level surface and se-
cure it against tipping. An unstably positioned diverter switch insert may
tip, resulting in injuries and damage.
5.
NOTICE!
Neither operate the diverter switch insert while removed nor
change the position of the tap selector coupling.Otherwise, the diverter
switch insert may be damaged when being reinstalled.
6.9.2.1.8