6 Assembly: Bell-type tank design
Maschinenfabrik Reinhausen GmbH 2015
135
4349315/00 EN
VACUTAP® VR®
2.
Insert position-indication disk horizontally between panel and bracket
and fit cover disk. Align tap position indicator disc and cover disk to pro-
duce a continuous red line.
Figure 167: Inserting position-indication disk
3.
Secure cover disk with countersunk head screw. The countersunk head
screw must be suitable for center-punching.
Figure 168: Fastening cover disk
4.
Secure countersunk head screw by center-punching.
Securing on-load tap-changer head cover
1.
NOTICE!
Place the on-load tap-changer head cover on the on-load tap-
changer head and take care not to damage the o-ring inserted in the on-
load tap-changer head cover. A damaged o-ring will cause oil to escape
6.8.8
Содержание VACUTAP VR
Страница 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Страница 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Страница 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Страница 266: ......
Страница 267: ......