6 Assembly: Bell-type tank design
Maschinenfabrik Reinhausen GmbH 2015
152
4349315/00 EN
VACUTAP® VR®
8.
Check the distance between the upper edge of the diverter switch insert
coupling tube and the on-load tap-changer head flange. The distance is
10 ± 2 mm (cover mounting and bell-type tank mounting).
Figure 197: Distance between the upper edge of the coupling tube and the on-load
tap-changer head flange
Inserting oil suction pipe
NOTICE
Damage to the on-load tap-changer!
Damage to the on-load tap-changer and oil suction pipe due to incorrect or-
der of installation.
► Strictly adhere to the order of installation. Make sure to always install
the diverter switch insert before inserting the oil suction pipe into the oil
compartment.
1.
Insert the oil suction pipe into the on-load tap-changer head.
Figure 198: Inserting oil suction pipe
6.9.2.3.2