6 Assembly: Bell-type tank design
Maschinenfabrik Reinhausen GmbH 2015
128
4349315/00 EN
VACUTAP® VR®
flange are used to lift the on-load tap-changer, the screws may be dam-
aged, which makes it impossible to properly screw the on-load tap-
changer and the on-load tap-changer head together!
Figure 152: Lifting device
2.
NOTICE!
Swing claws of lifting device outwards, use lifting device to lift
on-load tap-changer. Make sure that the triangle markings on the sup-
porting flange and on-load tap-changer head match up so that all sup-
porting flange stud bolts go easily through the mounting holes of the on-
load tap-changer head. Inaccurate alignment of on-load tap-changer
head to supporting flange will damage the on-load tap-changer.
Figure 153: Lifting on-load tap-changer