8 Fitting protective devices and drive components
Maschinenfabrik Reinhausen GmbH 2015
177
4349315/00 EN
VACUTAP® VR®
Making the electrical connections for the pressure-operated
relay
DANGER
Risk of fatal injury due to electric shock!
Failure to disconnect the switch housing or junction box from the power grid
before opening can result in electric shock!
► Disconnect the switch housing or junction box from the power grid be-
fore opening.
WARNING
Risk of severe injury or death!
Risk of severe injury or death from improperly making the electrical connec-
tions for the pressure-operated relay.
► Loop the pressure-operated relay into the trip circuit for the circuit
breaker of the transformer to be protected such that the circuit breaker
de-energizes the transformer immediately when the pressure-operated
relay is tripped.
► Circuits where only an alarm message is generated are not permitted.
1.
Remove the cover cap.
2.
Insert a M25x1.5 cable gland.
Use the tapped hole for routing lines for this.
3.
Connect the lines to the terminals of the snap-action switch.
The snap-action switch is designed as a normally open and normally
closed switch; it flips after being triggered and can be reset.
4.
Connect all of the electrical lines and the protective conductor.
Either 1 or 2 lines can be connected per terminal for the line connection
(Ø 0.75…2.5 mm²).
5.
Secure the cover cap.
6.
Ensure the fixing screw is positioned correctly, see Appendix.
8.3.3
Содержание VACUTAP VR
Страница 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Страница 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Страница 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Страница 266: ......
Страница 267: ......