App
- 15
Appendix 4 Sample Programs when Using CC-Link
Appendix 4.3 Devices Used in Programs
APPENDICES
(3) Refresh Devices
In redundant systems, refresh of remote inputs (RX), remote outputs (RY) and remote
registers (RWr, RWw) are set with the program.
Refresh settings of special relays (SB) and special registers (SW) are configured with
network parameters.
The CC-Link refresh devices and refresh ranges for the system in Appendix 4.1 (using
5 stations) are shown in Table App.12.
Change the transfer range on the CC-Link side, and the device range on the CPU
side to match them with the number of stations and module types on the system used.
* 1: Indicates the number of transferred data that is specified in the BMOV instruction.
Table App.12 Refresh Devices
CC-Link Side
CPU Side
Device Name
Transfer Range
Buffer Memory Head
Address
Number of Data
Transferred (Words)
*1
Device Used
Remote Input (RX)
RX0-RX9F
224(E0
H
)
10
X1000-X109F
Remote Output (RY)
RY0-RY9F
352(160
H
)
10
Y1000-Y109F
Remote Register (RWr)
RWr0-RWr20
736(2E0
H
)
20
W1000-W1013
Remote Register (RWw)
RWw0-RWw20
480(1E0
H
)
20
W1100-W1113
Special Relay (SB)
SB0-SB1FF
-
-
SB400-SB5FF
Special Register (SW)
SW0-SW1FF
-
-