When switching power on again, switch power on more than five seconds after
switching power off. Failure to do so may cause an inrush current of higher than
the specified value to flow.
* 1 : Use "double-shielded coaxial cables" when configuring a coaxial bus system on a MELSECNET/H
remote I/O network.
Refer to the following manual for the double shielded coaxial cables.
Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O
network)
* 2 : Diagnostics includes PLC diagnostics, Ethernet diagnostics, CC IE Control diagnostics,
MELSECNET diagnostics, and CC-Link/CC-Link/LT diagnostics.
For details, refer to each network manual.
Restarting System
...Refer to
Power off the system and then power on again, or set the RESET/L.CLR switch of the CPU module
to the RESET position and then set it to the reset switch neutral position.
Error Check
...Refer to
Check if the "ERR." LED of the CPU module is OFF.
If the "ERR" LED is ON/flashing, check the error cause using the System Monitor or diagnostics of
GX Developer, and eliminate it.
Running CPU Module
...Refer to
(1) Set the RUN/STOP switch of the CPU module (the "CONTROL" LED is ON) to the RUN
position, and confirm that the "RUN" LED is ON.
(2) Confirm that the "ERR." LED of the CPU module is OFF.
If the "ERR." LED is ON/flashing, check the error cause using the System Monitor or
diagnostics
*3
of GX Developer, and eliminate it.
If the error is caused by the parameters or programs, correct the parameters or programs.
Restarting System
...Refer to
Power off the system and then power on again, or set the RESET/LCLR switch of the CPU module
to the RESET position and then set it to the reset switch neutral position.
Diagram 4.2 Procedure for Starting Up in Debug Mode
Complete