2
- 20
2.4 System Configuration Cautions
2
SYSTEM CONFIGURATION
(3) Modules where the number of mountable modules is restricted
The module where the number of mountable modules is restricted when the
redundant CPU is used is shown in Table2.4.
* 1: The number of mountable modules per system indicates the number of modules that can be
mounted on main base unit or extension base unit. Or, it indicates the number of modules that can
be mounted on either one of the systems when they are mounted on main base unit.
* 2: CC-Link IE Controller Network module or MELSECNET/H module cannot be mounted to the
extension base unit.
* 3: Possible only when the first five digits of serial number for the Redundant CPUs in both systems
are "09102" or higher and GX Developer version is 8.58L or later.
In other combinations, the number of mountable modules per system is 4.
POINT
If setting 5 or more at "No. of boards in module" in CC-Link network parameter of
GX Developer version 8.55H or earlier, the following error dialog box appears.
In this case, set 4 or less at "No. of boards in module".
Table2.4 Number of modules loaded
Applicable Module
Type
Limitation on the number of mountable
modules per system
*1
CC-Link IE Controller Network
module
*2
• QJ71GP21-SX
• QJ71GP21S-SX
Up to 2
Up to 4 in total
MELSECNET/H module
*2
• QJ71LP21-25
• QJ71LP21S-25
• QJ71LP21G
• QJ71LP21GE
• QJ71BR11
Up to 4 in total of PLC
to PLC network and
remote I/O network
modules
Ethernet module
• QJ71E71-B2
• QJ71E71-B5
• QJ71E71-100
Up to 4
CC-Link master module
• QJ61BT11N
Up to 8
*3