5.7 Memory Copy From Control System To Standby System
5
3) Select "Memory copy" on the Redundant operation screen of the Online dialog
box on GX Developer, and click the Execute button.
4) When the memory copy confirmation dialog box appears, click the "Yes"
button.
This transfers the control system data to the standby system.
Then, the "BACKUP" LED of the standby system CPU module will flash (red).
* 3: When memory copy begins, the "MEM. COPY EXE. (error code: 6410)" continuation error will
occur in the control system CPU module, and then the "STANDBY SYS. DOWN (error code:
6300)" continuation error will occur.
* 4: When memory copy begins, the "PRG. MEM. CLEAR (error code: 6400)" stop error will occur in
the standby system CPU module.
Diagram 5.80 Redundant Operation Screen
Diagram 5.81 Confirmation Dialog Box Displayed on GX Developer
Diagram 5.82 LED Indications during Memory Copy