REDUNDANT SYSTEM FUNCTIONS
5.1 Basic Concept of Redundant System
5.1.4 System Consistency Check
5
- 22
1
OV
ER
VIE
W
2
SYS
TEM
CONFIGURA
TI
ON
3
TR
AC
KI
N
G
C
ABL
E
4
P
R
OCE
DURE
FO
R
S
TAR
TING
UP
A
RE
DUN
DAN
T
S
Y
S
T
E
M
5
RE
DUNDA
NT S
Y
S
T
E
M
FUNCTIONS
6
RE
DUN
DAN
T
S
Y
S
T
E
M
NE
TW
O
R
K
S
7
PR
OG
R
A
MM
IN
G
CA
UTIO
N
S
8
TR
O
U
BLE
S
HOOTING
(b) Inconsistency Errors
Table5.14 shows inconsistency errors that occur when the basic system
configurations are inconsistent.
If the "UNIT LAY. DIFF." error occurs in the standby system, configure the both
basic systems of the control system and standby system so that they will be
consistent in the followings.
• Model and type of modules mounted in the control system and standby
system main base units
• Network module mode settings
* 1: If a stop error occurs in the standby system CPU module, the following continuation error will
occur in the control system CPU module: "STANDBY SYS. DOWN (ERROR CODE: 6300)".
(4) System configuration check when using extension base unit
When the extension base unit is used, there are following restrictions. The error
description for the case where the system configuration does not meet the following
conditions is shown in Table5.15.
• Connect the redundant type extension base unit to the first extension stage.
• Only one redundant type extension base unit is applicable per system.
• Connect IN connector (IN1 and IN2) of the redundant type extension base unit to
OUT connector of the main base unit.
• Connect OUT connector of the redundant type extension base unit to IN
connector of the redundant power extension base unit.
• The main base units used in systems A and B should be the same model.
Table5.14 Basic System Configuration Inconsistency Errors
Execution Conditions
Error Description
• When both systems are powered ON
simultaneously
• When both system CPU modules are unreset
(RESET/L.CLR switch is set to the neutral
position) simultaneously
The following stop error will occur in the control
system and standby system CPU modules: "UNIT
LAY. DIFF. (error code: 6030 or 6035)".
• When one system starts up after the other.
• When the separate mode is changed to the
backup mode
• When reconnecting the tracking cable
The following stop error will occur in the standby
system CPU module only: "UNIT LAY. DIFF. (error
code: 6030 or 6035)".
*1
Table5.15 Error description when extension base unit does not meet use condition
Use condition
Error description
• Connect the redundant type extension base
unit to the first extension stage
• Properly connect the redundant type
extension base unit and the main base unit
"BASE LAY ERROR (error code: 2012 or 2013)" occurs.
Only one redundant type extension base unit is
applicable per system
"EXT.CABLE ERR. (error code: 2020)" occurs.
The main base units used in systems A and B
should be the same model
"BASE LAY ERROR (error code: 2012)" occurs.