8
8.3 Replacing Module in Redundant System
8.3.6 Main Base Unit Replacement Procedure
8
- 46
1
OV
ER
VIE
W
2
SYS
TEM
CONFIGURA
TI
ON
3
TR
AC
KI
N
G
C
ABL
E
4
P
R
OCE
DURE
FO
R
S
TAR
TING
UP
A
RE
DUN
DAN
T
S
Y
S
T
E
M
5
RE
DUNDA
NT S
Y
S
T
E
M
FUNCTIONS
6
RE
DUN
DAN
T
S
Y
S
T
E
M
NE
TW
O
R
K
S
7
PR
OG
R
A
MM
IN
G
CA
UTIO
N
S
8
TR
O
U
BLE
S
HOOTING
(2) Replacement Procedure
The replacement procedure for the main base unit is indicated in Diagram 8.34.
Confirming the Main Base Unit Targeted for Replacement
Confirm that the main base unit to be replaced is for the standby system (CONTROL LED is
off).When replacing the control system's power supply module, switch it to be the standby system
using GX Developer's system switching.
Refer to Section 5.2 regarding system switching via GX Developer.
Turn the Standby System's Power Supply OFF
Disconnect the Cable
1) Disconnect the tracking cable from the standby system CPU module.
Refer to Section 3.3, for disconnecting the tracking cable.
2) Disconnect the power supply cable from the standby system power supply module.
3) Disconnect the network cable from the network module.
Refer to the manual of the network module, for disconnecting the network cable.
4) Remove the connector/terminal block from the I/O module.
5) Disconnect the extension cable for mounting the main base unit of the standby system.
Removing Modules
Remove the modules from the main base unit.
Refer to the QCPU User's Manual (Hardware Design, Maintenance and Inspection), for
removing modules.
Replacing the Main Base Unit
1) Remove the main base unit from the control panel, etc.
2) Mount an alternative main base unit to the control panel, etc.
Mounting Modules
Mount the module that was removed from the previous base unit to the new one.
(Mount the modules to the main base unit so that they will be located the same as those of the
control system.)
Refer to the QCPU User's Manual (Hardware Design, Maintenance and Inspection), for
mounting modules.
Wiring
1) Connect the tracking cable to the standby system CPU module.
Refer to Section 3.3, for connecting the tracking cable.
2) Connect the power supply cable to the power supply module.
3) Connect the network cable to the network module.
Refer to the manual of the network module, for connecting the network cable.
4) Mount the terminal block/connector to the I/O module.
5) Connect the extension cable for mounting to the main base unit of the standby system.
Start