Appendix 5 Method for Starting up the Previous Control System
APPENDICES
2) Power supplies of both systems are temporarily OFF because of a power
failure, etc.
3) System A starts as the control system when both systems are
simultaneously powered ON.
(The SM1519 is ON for one scan after the system A CPU module has run.)
* 1: After turning on one of the power supply modules, turn the other one on within 3 seconds.
4) Switching System B to the control system through a system switching
instruction
Diagram App.16 The system when power supplies of both systems are
temporarily OFF
Diagram App.17 The system when both systems are simultaneously
powered ON
Diagram App.18 The system when System B is switched to the
control system through a system switching
instruction
Power ON OFF
System A
Power ON OFF
System B
Tracking cable
Power OFF ON
*1
Tracking cable
System A
Control system
System B
Standby system
SP.CONTSW K1 M0
GOEND
SP.CONTSW K1 M0
GOEND
Power OFF ON
*1
System A
Tracking cable
Standby system
System B
Control system
System switching